Description
The ControlByWeb® X-22S™ is an 8 analog input expansion module designed to add high-resolution analog measurement capability to an X-400™ or X-600M™ controller. Supporting multiple voltage ranges as well as 4–20mA current-loop sensors, the X-22S provides the flexibility needed for a wide variety of industrial and process instrumentation applications.
Engineered for accuracy and reliability, the X-22S is well suited for applications such as tank or bin level monitoring, flow and pressure measurement, and energy or environmental data acquisition. Multiple X-22S modules can be connected via ribbon cable to expand analog input capacity as needed, making it a versatile solution for flexible analog monitoring.
Key Features
- 8 Precision Analog Inputs: Adds eight high-resolution analog inputs to an X-400™ or X-600M™ controller.
- Multiple Input Types: Supports single-ended, differential, and 4–20mA (0–20mA) inputs.
- Multiple Voltage Ranges: Compatible with ±1.28V, ±2.56V, ±5.12V, and ±10.24V input ranges.
- 16-Bit SAR A/D Converter: Delivers accurate and reliable analog measurement performance.
- Reference Output: Includes a 5.0V reference output for powering potentiometers or resistance sensing devices.
- Expansion Bus Powered: Powered through the expansion bus with no separate power supply connections required.
- High Input Impedance: Supports flexible use with external resistors for extended input range options.
- Industrial Monitoring Applications: Ideal for environmental monitoring, wastewater systems, greenhouse applications, and more.
Specifications
| Technical Specification | Detail |
|---|---|
| Product Model | X-22S |
| Product Type | 8 Analog Input Expansion Module |
| Compatible Controllers | X-400™ or X-600M™ |
| Number of Inputs | 8 |
| Input Type | Single-ended, differential, 4–20mA (0–20mA), or a combination |
| Input Voltage Ranges | ±1.28V, ±2.56V, ±5.12V, ±10.24V, 4–20mA |
| Resolution | 16-bit, SAR |
| Reference Output Voltage | 5.00V |
| Reference Output Accuracy | 0.04% |
| Reference Temperature Coefficient | 3ppm/°C Max |
| Reference Current | 25mA max |
| Power Requirements | 9–28VDC (supplied via the X-400 controller, 24V recommended) |
| Current Draw at 9 VDC | 42 mA (voltage mode) / 83 mA (current mode) |
| Current Draw at 12 VDC | 32 mA (voltage mode) / 62 mA (current mode) |
| Current Draw at 24 VDC | 17 mA (voltage mode) / 33 mA (current mode) |
| Connectors | Inputs: 14-position, 3.81mm terminal spacing, removable, for 16–28 AWG wire Expansion Connector: Ribbon cable, 10-conductor, polarized, 2×5-position, 0.100″ pitch, RS-485 communications |
| LED Indicators | 1 LED: Power on |
| Dimensions | 1.41 in W x 3.88 in H x 3.1 in D (35.7 x 98.5 x 78 mm, not including connector) |
| Weight | 5 oz (142 g) |
| Enclosure Material | Lexan 940 Polycarbonate Plastic |
| Flame Rating | UL94 V0 |
| Operating Temperature | -40°C to 50°C (-40°F to 122°F) |
| Storage Temperature | -40°C to 85°C (-40°F to 185°F) |
| Humidity | 5–95%, non-condensing |
| Installation Location | Indoor use or NEMA-4 protected location |
| Electromagnetic Compliance | IEC CISPR 22, CISPR 24, FCC 47CFR15 (Class B), EN55024 ITE Immunity (2010), EN55022 Emissions (2010) |












Reviews